Junction box / Enclosure
Signaling device
Other equipment
Junction box / Enclosure
Signaling device
Other equipment
< Product < Industrial (ºñ¹æÆø)
UPS

 

Single-phase

3-phases

Output Power Rating

0.5~20 KVA

10~100 KVA

Material

Sheet steel

Finish

Painted in blue green color (Maker standard)

Efficiency (%)

Over 85%

Enclosure Protection

IP23

Humidity

Max 95% (Non-Condensing)

Operating Temperature

0 ¡É ~ 40 ¡É

Storage Temperature

-15 ¡É ~ 50 ¡É

Input wiring

1PH 2Wire / 3PH 3Wire

3PH

Input Voltage

220VAC~690VAC

220~380VAC

Input Voltage Range

+10% ~ -15%

Input Frequency

50Hz / 60Hz ¡¾ 5%

Input Power Factor

Over 0.99

Input THD

Current: Within 5%, Voltage: Within 2%

Input current limit

(Soft Start)

Battery Test

Automatic or Manual (Programmable)

Output wiring

1PH 2Wire

3PH

Output Voltage

220VAC~380VAC

110~220VAC

Output Voltage Stability

¡¾ 2%

Battery Charging Current Limitation

10% of Battery Volume (Programmable)

Control

SVPWM with high switching frequency (7.8125kHz) & IGBT

Transfer Time

Within 4ms

Rated output Voltage

3PH 110 ~ 220V

Output Voltage Stability

Within ¡¾1%

(THD)

Within ¡¾3%

Rated output frequency

50Hz / 60Hz

Stability of Output Frequency

¡¾0.1% (free-running)

Power factor range

0.8Lag

Overload Capacity

125% (10min), 150% (1min)